Parameter guide
95M-200
GAS-FIRED DIRECT VENT
MODULATING HOT WATER BOILER
P/N 240006105, Rev. B [06/08]
Revise boiler control parameters only if you
fully understand the purpose and result of the
changes and on the advice of Technical Support.
Tampering without understanding the control
settings in this manual will void the warranty
and can result in unreliable operation, with pos-
sible severe personal injury, death, or substan-
tial property damage.
WARNING
!

heating installer or service technician. Read all
instructions, including the Installation Manual
(P/N# 240006103), the Control Manual and Oper-
ating Instructions (P/N# 240006104), the Users
Information Manual (P/N# 240006106), and this
Parameter Guide before attempting to program
the control, and be sure to perform all steps in
-
sult in severe personal injury, death, or substan-
tial property damage.
WARNING
!
IMPORTANT: Installation must comply
with local requirements and with the Na-

installations or CSA B149.1 or B149.2 for
Canadian installations.
DO NOT DESTROY THESE INSTRUCTIONS!!
Please read carefully and keep in a safe place
for future reference.
Seitenansicht 0
1 2 3 4 5 6 ... 19 20

Inhaltsverzeichnis

Seite 1 - Parameter guide

Parameter guide95M-200GAS-FIRED DIRECT VENTMODULATING HOT WATER BOILER P/N 240006105, Rev. B [06/08]Revise boiler control parameters only if you

Seite 2

10Space heating differentials (parameters 22 and 23)The term “differential” is also referred to as “hysteresis.”• Parameter 22 is the “On” differentia

Seite 3

11Press and hold the “STEP” button.1. While holding the “STEP” button down, press and hold 2. the “MODE” button

Seite 4

12Para. NameRange Boiler DisplayDescriptionGascom SoftwareBoilerDisplayDisplay Position1st 2nd 3rd 4th1 T3 SetStorage DHW: 68° to 158°FInstantaneous

Seite 5

13Para. NameRange Boiler DisplayDescriptionGascom SoftwareBoilerDisplayDisplay Position1st 2nd 3rd 4th8T4 Frost Protection-22° to 50°F -22 to 50Initia

Seite 6 - 

14Para. NameRange Boiler DisplayDescriptionGascom SoftwareBoilerDisplayDisplay Position1st 2nd 3rd 4th17Minimum fan speed DHW2250 to 600022 to 60 (100

Seite 7 - Parameter 10 (T blocking)

15Para. NameRange Boiler DisplayDescriptionGascom SoftwareBoilerDisplayDisplay Position1st 2nd 3rd 4th26DHW detec-tion differen-tial ON-2° to 54°F -2

Seite 8 - Boost operation

16Para. NameRange Boiler DisplayDescriptionGascom SoftwareBoilerDisplayDisplay Position1st 2nd 3rd 4th34(1st digit)2nd CHcircuit CH type0 to 8 (see ri

Seite 9

17Para. NameRange Boiler DisplayDescriptionGascom SoftwareBoilerDisplayDisplay Position1st 2nd 3rd 4th35 (1st digit)3-Way Valve 0 to 2

Seite 10 - Figure #4

18Para. NameRange Boiler DisplayDescriptionGascom SoftwareBoilerDisplayDisplay Position1st 2nd 3rd 4th36Manual fans-peed-1 (auto op-eration)0 to 100 (

Seite 11

19Parameter No. ChangedOriginal Date of ChangeReason for Parameter Change

Seite 14

3IMPORTANT: Read the following instructions completely before installing!!Keep this manual near boilerand retain for future reference.PARAMETER GUIDEP

Seite 15

4This manual includes detailed explanations of the adjustable parameters. See Section II

Seite 16

5DO NOT CHANGE ANY PARAMETER UNLESS THE APPLICATION REQUIRES SPECIAL SETTINGS.PARAMETER/DESCRIPTION GASCOM 1 T3 Set DHW 150°F 1502 DHW System O

Seite 17

6OUTDOOR RESET OPERATIONOutdoor reset adjusts the supply water temperature so the heat output from the heating units matches the heat loss as the outd

Seite 18

7perature is less than T4 Minimum (Parameter 6).T1 Foot (Parameter 5) is the outlet water temperature the boiler tries to maintain whenever the outsid

Seite 19 - 

8greater than the value of Parameter 4 (T1 Top). There is no concern that temperature boost would supply water too hot for low-temperature systems, su

Seite 20

9% Rate BTUH RPM Boiler Display40 80,000 2250 2250 100,000 3250 3260 120,000 3800 3870 140,000 4400 4480 160,000 4750 4790 1