P/N 240008957, Rev. B [04/2013]
Converting Boiler From Natural Gas To LP:
1.
Follow instructions To TURN OFF GAS TO APPLIANCE
found on Operating Instructions label on boiler or in
Installation, Operation & Maintenance Manual. Verify all
electrical power to boiler is turned off.
WARNING
Electrical shock hazard. Turn OFF electrical power
supply at service panel.
!
2.
Remove upper jacket from boiler.
3.
Follow instruction TO TURN OFF GAS TO APPLIANCE.
Verify electrical power is OFF.
4.
Remove screws as shown in gures 1 & 2. Carefully
separate gas valve.
5.
Insert LP ori ce as shown in gures 1 & 2. See Table 1
for ori ce size.
6.
050 Mbh thru 200, O-ring gasket shown in gure 1 must
remain in place.
7.
Connect gas valve using previously removed screws.
8.
Place "Natural to LP" and "Converted by" labels onto
boiler as shown in gures 4 & 5.
9.
Replace upper jacket.
10.
Follow instructions in “Start-up Procedure” section of
boiler's Installation, Operation & Maintenance Manual for
proper startup and veri cation procedures.
Figure - 1 Disconnect Venturi Body from Gas Valve
050/075/100/150/200
TORX OR
ALLEN SCREW
HEAD 3 REQ'D.
VENTURI
BRASS LP ORIFICE
O-RING GASKET
GAS VALVE
CONVERSION KIT INSTRUCTIONS
NATURAL GAS TO LP & LP TO NATURAL GAS
050 Kit #550002303,
075 Kit #550002304,
100 Kit #550002305,
150 Kit #550002306,
200 Kit #550002307
299 Kit #550002799
WARNING
Fire, explosion, asphyxiation and electrical shock
hazard. Improper installation could result in death or
serious injury. Read this instruction and understand
all requirements, including requirements of authority
having jurisdiction, before beginning installation.
Installation not complete until appliance operation
veri ed per Installation, Operation & Maintenance
Manual provided with boiler.
!
Kit installation shall be completed by quali ed agency.
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - CONVERSION KIT INSTRUCTIONS

P/N 240008957, Rev. B [04/2013]Converting Boiler From Natural Gas To LP:1. Follow instructions To TURN OFF GAS TO APPLIANCE found on Operating Instru

Seite 2 - WARNING

2Converting Boiler From LP To Natural Gas:1. Follow instructions To TURN OFF GAS TO APPLIANCE found on Operating Instructions label on boiler or in In

Seite 3

3Figure - 4 Conversion Label Placement, 050/075/100/150/200Rating PlatePlace Conversion Labels HereLighting InstructionsFigure - 5 Conversion Label

Seite 4

Table 2 - Parts Lists100 Gas Conversion Kit #550002305DESCRIPTION PART # QTYOrifi ce, LP, 4.6mm 240008263 1Label, "Converted By" 240008688 2L